APC UPS电源SMT1000I-CH 1000VA/700W 在线互动式 内置电池 塔式安装
Overview
The Main Outlet Group and the Controlled Outlet Group can be configured to independently turn off,
turn on, shut down, and reboot connected equipment. (These features are not available on the 500 VA or 750 VA
units.)
The Main and Controlled Outlet Groups can be configured to do the following:
• Turn off: Disconnect from power immediately and restart only with a manual command.
• Turn on: Connect to power immediately.
• Shutdown: Disconnect power in sequence, and automatically reapply power in sequence when utility power
becomes available.
• Reboot: Shut down and restart.
In addition, the Main Outlet Group and the Controlled Outlet Group can be configured to do the following:
• Turn on or off in a specified sequence
• Automatically turn off or shut down when various conditions occur
Note: If the Main and Controlled Outlet Groups are not configured, all of the outlets on the unit will still provide
battery backup power.
Using the Main and Controlled Outlet Groups
The Main Outlet Group functions as a master switch. It will turn on first when power is applied, and shut down last
when there is a power outage and battery runtime has been exhausted.
The Main Outlet Group must be turned on for the Controlled Outlet Group to turn on.
1. Connect critical equipment to the Main Outlet Group.
2. Connect peripheral equipment to the Controlled Outlet Group.
– Nonessential equipment that should shut down quickly in the event of a power outage can be added to a
short power off delay, to conserve battery runtime.
– Equipment that has dependent peripherals that must restart or shut down in a specific order should be
connected to a separate outlet group.
– Equipment that needs to reboot independently from other equipment should be added to a separate
outlet group.
3. Use the Configuration menus to set reaction of the Controlled Outlet Group in the event of a power
outage.
SUA1000ICH-45
产品特点
APC公司的Smart-UPS,1000VA,LCD,230V,适用于中国
冷启动能力
当市电停止时提供临时的电池供电
能源计量表
为有节能意识的用户提供实际用电量(以千瓦时为单位)。
散热附件
正在申请工作模式,该模式绕过电源处于良好状态的未用